Model No.: KNLE1-100
Jenama: Korlen
Breaking Capacity: Low Voltage Circuit Breakers
Operation: Manual Type
Speed: Normal Type Circuit Breaker
Arc-extinguishing Medium: Air
Installation: Fixed
Structure: Elcb
Poles Number: 2
Type: Circuit Breaker
Function: Conventional Circuit Breaker
Certification: Ce
Rated Worling Current: 63;80;100a
Frame: 100a
Maximum Operating Time: I△n T≤0.1s , 5i△n T≤0.04
Sensibility: Ac Type
Rated Working Voltage: 240/415v
Pembungkusan: Karton
Produktiviti: 5000000PCS/Year
Pengangkutan: Ocean,Land,Air
Tempat asal: Wenzhou; Zhejiang; China
Sijil: CE,CB;VDE;
Kod HS: 8536200000
Port: Ningbo,ShangHai
Jenis bayaran: L/C,T/T,D/P,Paypal
RCBO adalah pemutus litar semasa sisa dengan perlindungan overcurrent. Pada asasnya, ia melaksanakan fungsi MCB dan RCCB bersama -sama. Ini bermakna, ia boleh digunakan untuk melindungi garis daripada yang terlalu banyak dan litar pintas serta perubahan yang jarang berlaku dalam keadaan normal.
Pemutus litar kebocoran siri KNLE1-100 digunakan pada garis sehingga 230V untuk fasa tunggal atau sehingga 400V untuk tiga fasa dengan arus yang dinilai sehingga 63A untuk bertindak sebagai perlindungan kebocoran. Di mana seseorang mendapat kejutan elektrik atau arus kebocoran di garisan melebihi nilai yang ditetapkan, pemutus litar secara automatik boleh memecahkan kuasa pada 0.2s untuk melindungi badan dan peralatan.
Pemutus litar kebocoran siri KNLE1-100 melakukan perlindungan kelebihan dan litar pintas dan juga melakukan kekerapan rendah litar beralih di bawah keadaan normal. Produk ini mematuhi keperluan piawaian GB16917.1.
Pemutus litar kebocoran bumi
Pemutus litar kebocoran
ELCB
Frame class | 100A |
Rated working voltage | 240/415V |
Rated frequency | 50/60Hz |
Rated working current | 63,80,100A |
Rated residual operating current | 0.03,0.1A |
Rated residual un-operating current | 0.015,0.05A |
Sensibility | AC Type |
Maximum operating time | IΔn t≤0.1s , 5IΔn t≤0.04 |
Instant release type | C type |
Limiting value of un-operating current | 6In |
Rated limiting short-circuit current | 6000A |
Pole number | 1P+N,2P,3P,3P+N |
Mechanical life | 8000 |
Electric life | 4000 |
Sequence NO . |
Release |
Test current I/In |
Start state |
Tripping time |
Expected restlt |
1 | c | 1.13In | Cold state | t≤2h | Not tripping |
2 | c | 1.45In |
Start right after the serial NO . 1 test |
t<2h | Tripping |
3 | c | 2.55In | Cold state | 1s<t<120s | Tripping |
4 | c | 5In | Cold state | t≤0.1s | Not tripping |
5 | c | 10In | Cold state | t<0.1s | Trippi |